(Created page with "<center><font size=3>'''Table summarizing specifications for materials under the pavement surface.'''</font size><br> Link to this [[Specifications for materials under permeab...") |
m |
||
Line 10: | Line 10: | ||
<tr> | <tr> | ||
<td>Bedding/choker layer</td> | <td>Bedding/choker layer</td> | ||
− | <td>*Pervious concrete: None | + | <td> |
+ | *Pervious concrete: None | ||
*Porous asphalt: 1inch of AASHTO No. 57 stone | *Porous asphalt: 1inch of AASHTO No. 57 stone | ||
*PICP: 2 inches of AASHTO No. 8 stone (MnDOT 3127FA-3)</td> | *PICP: 2 inches of AASHTO No. 8 stone (MnDOT 3127FA-3)</td> | ||
Line 17: | Line 18: | ||
<tr> | <tr> | ||
<td>Reservoir Layer</td> | <td>Reservoir Layer</td> | ||
− | <td>*Pervious concrete: AASHTO No. 57 stone or per hydraulic design | + | <td> |
+ | *Pervious concrete: AASHTO No. 57 stone or per hydraulic design | ||
*Porous asphalt:AASHTO No. 2, 3, or 5 stone | *Porous asphalt:AASHTO No. 2, 3, or 5 stone | ||
*PICP: 4 inches of AASHTO No. 57 base and AASHTO No.2, 3 or 4 stone subbase</td> | *PICP: 4 inches of AASHTO No. 57 base and AASHTO No.2, 3 or 4 stone subbase</td> |
Bedding/choker layer |
|
Washed free of fines |
Reservoir Layer |
|
Stone layer thickness based on the pavement structural and hydraulic requirements. Stonewashed and free of fines. Recommended minimum void ratio = 0.4. |
Underdrain (optional) | Use 4 to 6 inch diameter perforated PVC (AASHTO M-252) pipe or corrugated polyethylene pipe. Perforated pipe installed for the full length of the permeable pavement cell, and non-perforated pipe, as needed,connected to storm drainage system. | |
Filter Layer (optional) | Sand filter layeris separated from base above and native soils with geotextile. Sand layer typically ASTM C33 gradation, 6 to 12 inches thick. | The sand layer may require a choker layer on surface to provide transition to base layerstone. |
Geotextile(optional) | Comply with AASHTO M-288 Standard Specification for Geotextile Specification for Highway Applications, drainage and separation applications, Class I or II. Porous asphalt industry recommends non-woven geotextile. | |
Impermeable Liner | Use a minimum 30mil PVC liner covered by 12 ounce/square yard non-woven geotextile. EPDM andHDPE liner material is also acceptable. | |
Observation Well | Use a perforated 4 to 6 inch vertical PVC pipe (AASHTO M-252) with a lockable cap, installedflush with the surface (or under pavers). |