(Created page with "The following are ''RECOMMENDED'' for infiltration practices with underdrains. *The minimum pipe diameter is 4 inches. *Install 2 or more underdrains for each infiltration sys...") |
m |
||
Line 7: | Line 7: | ||
*Include a utility trace wire for all buried piping. | *Include a utility trace wire for all buried piping. | ||
*For underdrains that daylight on grade, include a marking stake and animal guard; | *For underdrains that daylight on grade, include a marking stake and animal guard; | ||
− | *For each underdrain have an accessible knife gate valve on its outlet to allow the option of operating the system as either an infiltration system, filtration system, or both. The valve should enable the ability to make adjustments to the discharge flow so the sum of the infiltration rate plus the under-drain discharge rate equal a 48 hour draw-down time. | + | *For each underdrain have an accessible knife gate valve on its outlet to allow the option of operating the system as either an [[Glossary#I|infiltration]] system, [[Glossary#F|filtration]] system, or both. The valve should enable the ability to make adjustments to the discharge flow so the sum of the infiltration rate plus the under-drain discharge rate equal a 48 hour draw-down time. |
*Perforations should be 3/8 inches. Use solid sections of non-perforated PVC piping and watertight joints wherever the underdrain system passes below berms, down steep slopes, makes a connection to a drainage structure, or daylights on grade. | *Perforations should be 3/8 inches. Use solid sections of non-perforated PVC piping and watertight joints wherever the underdrain system passes below berms, down steep slopes, makes a connection to a drainage structure, or daylights on grade. | ||
*Spacing of collection laterals should be less than 25 feet. | *Spacing of collection laterals should be less than 25 feet. |
The following are RECOMMENDED for infiltration practices with underdrains.
The procedure to size underdrains is typically determined by the project engineer. An example for sizing underdrains is found in Section 5.7 of the North Carolina Department of Environment and Natural Resources Stormwater BMP Manual.