==Standards and specifications== | ==Standards and specifications== | ||
− | + | [https://standardplates.dot.state.mn.us/ MnDOT Standard Plates] 3133D and 3134D provide standard detail for “Riprap at RCP Outlets” and “Riprap at CSP Outlets”], respectively (effective date: 8/6/2014). | |
The [https://www.dot.state.mn.us/pre-letting/spec/ MnDOT Standard Specifications for Construction] (2016 edition) Specification 2573.3.L (Culvert End Controls) states that culvert outlet ends must be protected with “energy dissipation devices, transition devices, or both to reduce erosion and sediment loss while reducing the velocity of water existing culvert.” Specifications 2501 (Pipe Culverts) and 2503 (Pipe Sewers) may also be applicable depending on the BMP/device chosen. Additional materials specifications that may be applicable include Specifications 2511 and 3601 (Riprap), and 3733 (Geotextile). The 2016 edition of the [http://www.dot.state.mn.us/pre-letting/spec/ MnDOT Standard Specifications for Construction]. | The [https://www.dot.state.mn.us/pre-letting/spec/ MnDOT Standard Specifications for Construction] (2016 edition) Specification 2573.3.L (Culvert End Controls) states that culvert outlet ends must be protected with “energy dissipation devices, transition devices, or both to reduce erosion and sediment loss while reducing the velocity of water existing culvert.” Specifications 2501 (Pipe Culverts) and 2503 (Pipe Sewers) may also be applicable depending on the BMP/device chosen. Additional materials specifications that may be applicable include Specifications 2511 and 3601 (Riprap), and 3733 (Geotextile). The 2016 edition of the [http://www.dot.state.mn.us/pre-letting/spec/ MnDOT Standard Specifications for Construction]. |
Permanent or temporary energy dissipators prevent erosion, turbulence, and turbidity where stormwater pipes or ditches discharge to unprotected areas, such as channel banks, slopes, or upslope outfall locations. Their main purpose is to reduce the speed of concentrated flows to prevent scour at conveyance outlets. This practice is also called Scour Protection or Outlet Protection. Common types of outlet protection devices include concrete aprons, riprap-lined basins, and settling basins.
Energy dissipators intercept incoming flows from pipes and ditches to deflect, scatter, or otherwise neutralize the erosive force of concentrated, moving stormwater. These structures are intended to protect soil from turbulence and high velocities, which can otherwise cause scour erosion. They typically consist of a structural apron lining fabricated from riprap, concrete, turf reinforcement mats, or other structural materials. Certain types of basins (e.g., settling/stilling/impact basins) can also function as energy dissipators. Many of these techniques are effective and relatively inexpensive and easy to install. Energy dissipators require careful design based on the hydraulic forces of concentrated flows exiting pipes and ditches.
Energy dissipators at pipe and ditch outlets are appropriate for any unpaved or otherwise non-armored location where concentrated flows are discharged to areas subject to erosion.
Energy dissipators are used where concentrated flows are discharged against channel banks, on poorly stabilized slopes, or onto upslope areas that are not protected against erosive flows. They are appropriate at the outlets of ponds, pipe slope drains, culverts, ditches, or other conveyances, and where runoff is conveyed to a natural or manmade drainage feature such as a stream, wetland, lake, or ditch. The most common applications include riprap aprons at culvert outlets, ditches lined with turf reinforcement matting, and stilling or impact basins designed to accept and dissipate high-energy stormwater flows. Some important considerations when selecting energy dissipators for a site include the following.
The Construction Stormwater general permit has several requirements pertaining to sediment control practices.
Properly installed temporary and permanent energy dissipators are effective in preventing channel bank scour, slope gullying, and plunge pool erosion where concentrated flows discharge into unarmored, poorly stabilized areas.
Expected performance for outlet energy dissipators
Link to this table
Water Quantity | |
---|---|
Flow attenuation | Little or no design benefit |
Runoff volume reduction | Little or no design benefit |
Water Quantity | |
Pollution prevention | |
Soil erosion | Primary design benefit |
Sediment control | Secondary design benefit |
Nutrient loading | Little or no design benefit |
Pollutant removal | |
Total suspended solids | Secondary design benefit |
Total phosphorus | Little or no design benefit |
Heavy metals | Little or no design benefit |
Floatables | Little or no design benefit |
Oil and grease | Little or no design benefit |
A review, analysis, and evaluation of both the location and magnitude of concentrated flows associated with culvert, ditches, and channel discharges can help identify where scour and other erosion are likely to occur. Culvert outlets are common places where energy dissipators are needed, as are locations where ditches discharge to terraces or slopes that are not armored against erosive, concentrated flows. In cases where flow velocities are too high for the economical use of an apron, a stilling basin or impact basin may be more appropriate. These structures dissipate energy from high-velocity flows to an acceptable level before discharging to an outlet channel.
Energy dissipator design and installation instructions can usually be included in the construction/installation plans for pipes, ditches, and channels. For example, culverts can be outfitted with outlet riprap aprons during installation, and ditches discharging into larger channels can be designed to include appropriate turf reinforcement matting and/or other structural elements where small, high-velocity ditches discharge against poorly armored banks of larger channels.
Key planning considerations for large projects – especially those involving mass clearing and grading – include 1) minimizing the number and magnitude of concentrated flows during initial clearing and grading, to the extent possible; and 2) installing permanent drainage features (e.g., stabilized ditches, channels, energy dissipators, vegetated channel buffers, etc.) as early as possible, especially since installing, stabilizing, and maintaining temporary drainage infrastructure is expensive and time-consuming. Following these two recommendations can reduce construction costs and increase the overall efficiency of sediment and erosion control on a site.
Due to their proximity to surface water locations, many energy dissipation practices are installed in areas subject to state, federal, or local permits. For example, where energy dissipation materials are installed within waters of the U.S., permit coverage from the U.S. Army Corps of Engineers under Section 404 of the Clean Water Act and water quality certification from MPCA under Section 401 of the Clean Water Act is required.
Temporary energy dissipators at construction sites, which often include riprap aprons, are designed for short-term (e.g., less than one year) erosion control during the construction period. Design of permanent dissipators will be driven by erosive force estimates and the final aesthetics desired at the dissipator location. For example, highway and industrial areas may be suitable sites for the use of riprap aprons or concrete structures at culvert outlets, while the softer look of vegetation growing through underlying turf reinforcement mats may be more appropriate for some commercial and residential areas. Temporary devices should be completely removed as soon as the surrounding drainage area has been stabilized.
In general, dissipator design focuses on a few key variables: flow velocity, flow depth, and culvert or ditch characteristics (e.g., type, size, shape, roughness), as well as approaches for spreading out the outlet flow, deflecting it via armored surfaces, absorbing its energy in a stilling or impact basin, or roughening flow paths to reduce erosive forces. A properly designed riprap apron employs several of these approaches including spreading the flow and deflecting and roughening its movement through the use of adequately sized rock. The subsections below provide summary design information and references for designing a variety of energy dissipators. Alternative methods for energy dissipation can be found in the Federal Highway Administration’s HEC-14 (see Reference Materials).
Most outlet protection applications consist of a structural apron lining. Apron linings can be made of riprap, concrete, grouted riprap or other structural materials. Riprap aprons are best suited for temporary use during construction, while grouted or wire tied rock riprap can decrease maintenance requirements. As indicated above, in some cases flow velocities may be too high for economical use of an apron.
Outlet energy dissipators may or may not require a detailed design, depending upon the scope and complexity of the job. For outlets with very high velocities or very low tailwater conditions, outlet protection should be designed only by a qualified engineer. The following criteria are recommended for the design of structurally lined aprons below pipe outlets.
Example sizing information for riprap energy dissipators at culvert outlets. Source: Kentucky Division of Water
Link to this table
Culvert size | Avg. rock diameter | Apron width1 | Apron length2 | Apron length3 |
---|---|---|---|---|
8" | 3" | 2–3 ft. | 3–5 ft. | 5–7 ft. |
12" | 5" | 3–4 ft | 4–6 ft. | 8–12 ft. |
18" | 8" | 4–6 ft. | 6–8 ft. | 12–18 ft. |
24" | 10" | 6–8 ft. | 8–12 ft. | 18–22 ft. |
30" | 12" | 8–10 ft. | 12–14 ft. | 22–28 ft. |
36" | 14" | 10–12 ft. | 14–16 ft. | 28–32 ft. |
42" | 16" | 12–14 ft. | 16–18 ft. | 32–38 ft. |
48" | 20" | 14–16 ft. | 18–25 ft. | 38–44 ft. |
1Apron width at the narrow end (pipe or channel outlet)
2Apron length for slow-flow (no pressure head) culverts
3Apron length for high flow (pressure head) culverts
A stilling basin is an excavated pool of water that is lined with riprap and used to dissipate energy from high-velocity flow. An impact basin is a reinforced concrete structure that slows water velocities to an acceptable level before discharging water to an outlet channel. Riprap stilling basins and plunge pools reduce flow velocity rapidly. They should be considered as an alternative to riprap aprons where pipe outlets are cantilevered, or where high flows would require an excessive apron length. Where conditions warrant, other energy dissipators such as concrete impact basins may be considered.
Stilling basins are used to convert flows from supercritical to subcritical flow regimes by allowing a hydraulic jump to occur within the structure over a wide range of flow conditions and depths. A professional engineer must design energy dissipators and stilling basins using hydraulic computations. A primary operation and maintenance concern for both energy dissipators and stilling basins is the accumulation of sediment and trash.
MnDOT Standard Plates 3133D and 3134D provide standard detail for “Riprap at RCP Outlets” and “Riprap at CSP Outlets”], respectively (effective date: 8/6/2014).
The MnDOT Standard Specifications for Construction (2016 edition) Specification 2573.3.L (Culvert End Controls) states that culvert outlet ends must be protected with “energy dissipation devices, transition devices, or both to reduce erosion and sediment loss while reducing the velocity of water existing culvert.” Specifications 2501 (Pipe Culverts) and 2503 (Pipe Sewers) may also be applicable depending on the BMP/device chosen. Additional materials specifications that may be applicable include Specifications 2511 and 3601 (Riprap), and 3733 (Geotextile). The 2016 edition of the MnDOT Standard Specifications for Construction.
Inspect energy dissipators before periods of flow to ensure they are prepared to function. Inspect after flow periods (including stormwater runoff and runoff from snowmelt) to observe and document deficiencies. Inspection guidelines include the following.
Energy dissipation devices should be inspected periodically to check for scour, and any needed repairs should be completed promptly to prevent further damage. Below are typical maintenance practices.
Below is an estimated BMP cost based on MnDOT data summarizing average bid prices for awarded projects in 2014.
Except where more stringent requirements are presented in this guidance, BMPs shall comply with MnDOT and other state requirements. Primary design references include:
The following is a list of additional resources that are not specific to Minnesota: