[[file:Schematic of practices.png|300px|thumb|alt=schematic of infiltration practices|<font size=3>Schematic illustrating A)infiltration trench, B) underground infiltration, C) infiltration basin, and D) dry well.</font size>]] | [[file:Schematic of practices.png|300px|thumb|alt=schematic of infiltration practices|<font size=3>Schematic illustrating A)infiltration trench, B) underground infiltration, C) infiltration basin, and D) dry well.</font size>]] | ||
− | Stormwater [ | + | Stormwater <span title="Infiltration Best Management Practices (BMPs) treat urban stormwater runoff as it flows through a filtering medium and into underlying soil, where it may eventually percolate into groundwater. The filtering media is typically coarse-textured and may contain organic material, as in the case of bioinfiltration BMPs."> [https://stormwater.pca.state.mn.us/index.php?title=Stormwater_infiltration_Best_Management_Practices '''infiltration''']</span> practices capture and temporarily store stormwater before allowing it to infiltrate into the soil. Infiltration practices are applicable to sites with naturally permeable soils and a suitable distance to the seasonally high groundwater table, bedrock or other impermeable layer. They may be used in residential and other urban settings where elevated runoff volumes, pollutant loads, and runoff temperatures are a concern. Stormwater runoff having high pollutant loads should receive a significant amount of <span title="Pretreatment reduces maintenance and prolongs the lifespan of structural stormwater BMPs by removing trash, debris, organic materials, coarse sediments, and associated pollutants prior to entering structural stormwater BMPs. Implementing pretreatment devices also improves aesthetics by capturing debris in focused or hidden areas. Pretreatment practices include settling devices, screens, and pretreatment vegetated filter strips."> [https://stormwater.pca.state.mn.us/index.php?title=Pretreatment '''pretreatment''']</span> to protect the groundwater quality, particularly if soil infiltration rates are high (e.g. [http://stormwater.pca.state.mn.us/index.php/Design_infiltration_rates HSG A soils]). Runoff from potential <span title="Stormwater Hotspots (PSHs) are activities or practices that have the potential to produce relatively high levels of stormwater pollutants"> '''[https://stormwater.pca.state.mn.us/index.php?title=Potential_stormwater_hotspots stormwater hotspots]'''</span> (PSH) should not be introduced to infiltration areas. Infiltration should be avoided in areas with [http://stormwater.pca.state.mn.us/index.php/Stormwater_infiltration_and_contaminated_soils_and_groundwater contaminated soils or groundwater]. |
− | Design variants discussed on this page include the infiltration basin, the infiltration trench, the dry well and the underground infiltration system. To see overviews for other infiltration practices, see the following sections. | + | Design variants discussed on this page include the <span title="Infiltration basins, infiltration trenches, dry wells, and underground infiltration systems capture and temporarily store stormwater before allowing it to infiltrate into the soil. As the stormwater penetrates the underlying soil, chemical, biological and physical processes remove pollutants and delay peak stormwater flows."> [https://stormwater.pca.state.mn.us/index.php?title=Infiltration '''infiltration basin''']</span>, the infiltration trench, the dry well and the underground infiltration system. To see overviews for other infiltration practices, see the following sections. |
*[[Overview for bioretention]] | *[[Overview for bioretention]] | ||
*[[Overview for permeable pavement]] | *[[Overview for permeable pavement]] | ||
Line 15: | Line 15: | ||
==Function within stormwater treatment train== | ==Function within stormwater treatment train== | ||
− | The infiltration practices discussed on this page may be located at the end of the [ | + | The infiltration practices discussed on this page may be located at the end of the <span title="Multiple BMPs that work together to remove pollutants utilizing combinations of hydraulic, physical, biological, and chemical methods"> [https://stormwater.pca.state.mn.us/index.php?title=Using_the_treatment_train_approach_to_BMP_selection '''treatment train''']</span> or they can be designed as <span title="A stormwater system in which part or all of the stormwater runoff is diverted from the primary treatment practice. Partial diversion is employed for bypass runoff, which is runoff in excess of the designed treatment volume of the practice. Full offline diversion is employed as a temporary means to divert all runoff from a stormwater practice, typically to avoid erosion of exposed soil or establishment of vegetation."> '''offline'''</span> configurations where the <span title="The volume of water that is treated by a BMP."> [https://stormwater.pca.state.mn.us/index.php?title=Water_quality_criteria '''Water Quality Volume''']</span> is diverted to the infiltration practice. In any case, the practice may be applied as part of a stormwater management system to achieve one or more of the following objectives: |
*reduce stormwater pollutants | *reduce stormwater pollutants | ||
*increase groundwater recharge | *increase groundwater recharge | ||
*decrease runoff peak flow rates | *decrease runoff peak flow rates | ||
*decrease the volume of stormwater runoff | *decrease the volume of stormwater runoff | ||
− | *preserve | + | *preserve <span title="Baseflow (also called drought flow, groundwater recession flow, low flow, low-water flow, low-water discharge and sustained or fair-weather runoff) is the portion of streamflow delayed shallow subsurface flow".> '''baseflow'''</span> in streams |
− | *reduce | + | *reduce thermal impacts of runoff |
==MPCA permit applicability== | ==MPCA permit applicability== | ||
− | One of the goals of this Manual is to facilitate understanding of and compliance with the [ | + | One of the goals of this Manual is to facilitate understanding of and compliance with the [https://stormwater.pca.state.mn.us/index.php?title=Construction_stormwater_program General Stormwater Permit for Construction Activity (MN R100001)], commonly called the Construction General Permit (CGP), which includes design and performance standards for permanent stormwater management systems. These standards must be applied in all projects in which at least 1 acre of new impervious area is being created, and the permit stipulates certain standards for various categories of stormwater management practices. |
− | For regulatory purposes, infiltration practices fall under | + | For regulatory purposes, infiltration practices fall under Infiltration systems in the permit. If used in combination with other practices, credit for combined stormwater treatment can be given. Due to the statewide prevalence of the MPCA permit, design guidance in this section is presented with the assumption that the permit does apply. Also, although it is expected that in many cases infiltration will be used in combination with other practices, standards are described for the case in which it is a stand alone practice. |
The following terms are thus used in the text to distinguish various levels of stormwater pond design guidance. | The following terms are thus used in the text to distinguish various levels of stormwater pond design guidance. | ||
Line 36: | Line 36: | ||
'''RECOMMENDED:''' Indicates design guidance that is helpful for infiltration performance but not critical to the design. | '''RECOMMENDED:''' Indicates design guidance that is helpful for infiltration performance but not critical to the design. | ||
− | Of course, there are situations, particularly retrofit projects, in which an infiltration facility is constructed without being subject to the conditions of the MPCA permit. While compliance with the permit is not required in these cases, the standards it establishes can provide valuable design guidance to the user. It is also important to note that additional and potentially more stringent design requirements may apply for a particular | + | Of course, there are situations, particularly retrofit projects, in which an infiltration facility is constructed without being subject to the conditions of the MPCA permit. While compliance with the permit is not required in these cases, the standards it establishes can provide valuable design guidance to the user. It is also important to note that additional and potentially more stringent design requirements may apply for a particular infiltration facility, depending on where it is situated both jurisdictionally and within the surrounding landscape. |
{{alert|There is some concern that underground infiltration systems and dry wells meet the U.S. Environmental Protection Agency (EPA) definition of a [http://water.epa.gov/type/groundwater/uic/class5/index.cfm Class V injection well]. Class V injection wells are defined as any bored, drilled, or driven shaft, or dug hole that is deeper than its widest surface dimension, or an improved sinkhole, or a subsurface fluid distribution system (from U.S. Environmental Protection Agency, June 2003). Please consult [https://www.epa.gov/uic/class-v-wells-injection-non-hazardous-fluids-or-above-underground-sources-drinking-water EPA] with questions on the applicability of Class V injection well rules.|alert-info}} | {{alert|There is some concern that underground infiltration systems and dry wells meet the U.S. Environmental Protection Agency (EPA) definition of a [http://water.epa.gov/type/groundwater/uic/class5/index.cfm Class V injection well]. Class V injection wells are defined as any bored, drilled, or driven shaft, or dug hole that is deeper than its widest surface dimension, or an improved sinkhole, or a subsurface fluid distribution system (from U.S. Environmental Protection Agency, June 2003). Please consult [https://www.epa.gov/uic/class-v-wells-injection-non-hazardous-fluids-or-above-underground-sources-drinking-water EPA] with questions on the applicability of Class V injection well rules.|alert-info}} | ||
Line 76: | Line 76: | ||
==Special receiving waters suitability== | ==Special receiving waters suitability== | ||
− | The BMP design restrictions for special watersheds table below provides guidance regarding the use of infiltration practices in areas upstream of [ | + | The BMP design restrictions for special watersheds table below provides guidance regarding the use of infiltration practices in areas upstream of <span title="Waters with qualities that warrant extra protection"> [https://stormwater.pca.state.mn.us/index.php?title=Construction_stormwater_program#Special_Waters_and_Impaired_Waters '''special receiving waters''']</span>. |
− | {{:Infiltration | + | {{:Infiltration and filtration bmp design restrictions for special waters and watersheds}} |
==Cold climate suitability== | ==Cold climate suitability== | ||
− | Infiltration practices should remain effective water quality improvement systems for many years, even during winter conditions, if designed and constructed properly and it has been shown that hydraulic efficiency and infiltration rates can remain at levels used for design sizing. However, in cold climates, some special considerations are HIGHLY RECOMMENDED for surface systems to ensure sustained functionality and limit the damage freezing temperatures and snow and ice removal may cause. | + | [[File:Snow plowed and piled in parking lot.jpg|thumb|300px|alt=Photo showing Snow plowed and piled in parking lot|<font size=3>Snow plowed and piled in parking lot. Consideration should be given in locating these "snow dumps", since they will contribute a significant amount of stormwater runoff.]]</font size> |
+ | |||
+ | Infiltration practices should remain effective water quality improvement systems for many years, even during winter conditions, if designed and constructed properly and it has been shown that hydraulic efficiency and <span title="The infiltration rate is the velocity or speed at which water enters into the soil"> '''infiltration rates'''</span> can remain at levels used for design sizing. However, in cold climates, some special considerations are HIGHLY RECOMMENDED for surface systems to ensure sustained functionality and limit the damage freezing temperatures and snow and ice removal may cause. | ||
One concern with infiltration in cold weather is the ice that forms both over the top of the practice and within the soil structure, which can completely stop infiltration. To limit the effect of this problem, it is HIGHLY RECOMMENDED that the facility be actively inspected to ensure that it is properly drawing down before it freezes in the late fall. Adequate drawdown can be determined using one of the several field assessment techniques such as those recommended by the University of Minnesota Extension ([http://stormwaterbook.safl.umn.edu/infiltration-practices see section on Assessment]). If it is determined that stormwater runoff is not infiltrating prior to hard freeze, the BMP should be placed offline for correction in the spring. | One concern with infiltration in cold weather is the ice that forms both over the top of the practice and within the soil structure, which can completely stop infiltration. To limit the effect of this problem, it is HIGHLY RECOMMENDED that the facility be actively inspected to ensure that it is properly drawing down before it freezes in the late fall. Adequate drawdown can be determined using one of the several field assessment techniques such as those recommended by the University of Minnesota Extension ([http://stormwaterbook.safl.umn.edu/infiltration-practices see section on Assessment]). If it is determined that stormwater runoff is not infiltrating prior to hard freeze, the BMP should be placed offline for correction in the spring. | ||
Line 88: | Line 90: | ||
Proprietary, sub-grade infiltration systems provide an alternative to standard surface based systems. Essentially, these systems provide an insulated location for pre-treated snowmelt to be stored and slowly infiltrated, or simply filtered and drained away if groundwater sensitivity is an issue. The insulating value of these systems adds to their appeal as low land consumption alternatives to ponds and surface infiltration basins. | Proprietary, sub-grade infiltration systems provide an alternative to standard surface based systems. Essentially, these systems provide an insulated location for pre-treated snowmelt to be stored and slowly infiltrated, or simply filtered and drained away if groundwater sensitivity is an issue. The insulating value of these systems adds to their appeal as low land consumption alternatives to ponds and surface infiltration basins. | ||
− | For all | + | For all BMPs it is HIGHLY RECOMMENDED that snow and ice removal plans including predetermined locations for stockpiling be determined prior to or during the design process. Infiltration features cannot be used for significant snow storage areas as debris build-up, plant damage, and lower infiltration rates are likely to occur. Some snow storage unavoidable when BMPs are adjacent to areas where snow removal is required but it is critical that the property owner and snow and ice removal contractor have identified other areas for large scale snow storage. |
Excessive deicing agents have the potential to create a [http://stormwater.pca.state.mn.us/index.php/Potential_stormwater_hotspots hot spot] in some locations that could lead to reduced infiltration rates or concentrations that exceed surface water or groundwater standards. Locations such as busy intersections on slopes, parking garage ramps or on walkways near the entrances of commercial buildings are likely to be heavily treated with deicing agents to avoid slip and falls or vehicle collisions. This should be taken into consideration when siting any infiltration BMP. | Excessive deicing agents have the potential to create a [http://stormwater.pca.state.mn.us/index.php/Potential_stormwater_hotspots hot spot] in some locations that could lead to reduced infiltration rates or concentrations that exceed surface water or groundwater standards. Locations such as busy intersections on slopes, parking garage ramps or on walkways near the entrances of commercial buildings are likely to be heavily treated with deicing agents to avoid slip and falls or vehicle collisions. This should be taken into consideration when siting any infiltration BMP. | ||
Line 95: | Line 97: | ||
==Water quantity treatment== | ==Water quantity treatment== | ||
− | The amount of stormwater volume infiltrated depends on the design variant selected. Smaller infiltration practices (e.g. infiltration trenches) should either be designed off-line using a flow diversion, or designed to safely pass large storm flows while still protecting the infiltration area. In limited cases (e.g. extremely permeable soils), these smaller infiltration practices can accommodate the [ | + | The amount of stormwater volume infiltrated depends on the design variant selected. Smaller infiltration practices (e.g. infiltration trenches) should either be designed off-line using a flow diversion, or designed to safely pass large storm flows while still protecting the infiltration area. In limited cases (e.g. extremely permeable soils), these smaller infiltration practices can accommodate the [https://stormwater.pca.state.mn.us/index.php?title=Unified_sizing_criteria channel protection volume], V<sub>cp</sub>, in either an off- or on-line configuration. |
− | + | ||
− | + | In general, supplemental stormwater practices will be necessary to satisfy channel and flood protection requirements when smaller infiltration practices are used. However, these practices can help reduce detention requirements for a site through volume reduction. | |
+ | |||
+ | Due to their size, the larger infiltration practices (e.g. infiltration basins and underground infiltration systems) have the potential to provide greater water quantity benefits. Surcharge storage above the practice bottom is available for detention. Outlet structures can be sized to partially or fully accommodate larger storm peak discharge control while allowing the volume below the outlet to infiltrate. | ||
==Water quality treatment== | ==Water quality treatment== | ||
Line 104: | Line 108: | ||
There are few data available demonstrating the load reductions or outflow concentrations of larger-scale infiltration practices such as infiltration trenches. Similarly, few sampling programs collect infiltrating water that flows through an infiltration system. | There are few data available demonstrating the load reductions or outflow concentrations of larger-scale infiltration practices such as infiltration trenches. Similarly, few sampling programs collect infiltrating water that flows through an infiltration system. | ||
− | For properly designed, operated, and maintained infiltration systems, all water routed into them should be “removed” from stormwater flow, resulting in 100 percent efficiency relative to volume and pollutant reduction. For this reason, any infiltration BMP performance table should show all 100 percent entries for that portion of stormwater entering the infiltration system. This logic assumes that stormwater is the beneficiary of any infiltration system, but ignores the fact that pollution, if any remains after the internal workings of the infiltration BMP itself (see later discussion in this section), is being transferred into the shallow groundwater system. | + | For properly designed, operated, and maintained infiltration systems, all water routed into them should be “removed” from stormwater flow, resulting in 100 percent efficiency relative to volume and pollutant reduction. For this reason, any infiltration BMP performance table should show all 100 percent entries for that portion of stormwater entering the infiltration system. This logic assumes that stormwater is the beneficiary of any infiltration system, but ignores the fact that pollution, if any remains after the internal workings of the infiltration BMP itself (see later discussion in this section), is being transferred into the shallow groundwater system. See [[Surface water and groundwater quality impacts from stormwater infiltration]]. |
+ | |||
+ | Properly designed infiltration systems discussed later in this section will accommodate a design volume based on the required water quality volume. Excess water must be <span title="Stormwater runoff in excess of the design flow, which is diverted around a stormwater structure"> '''bypassed'''</span> and diverted to another BMP so that the design infiltration occurs within 48 hours if under state regulation, or generally within 72 hours under certain local and watershed regulations. In no case should the bypassed volume be included in the pollutant removal calculation. | ||
− | + | Data that are reported in performance literature for infiltration systems, unless reporting 100 percent effectiveness for surface water or documenting outflow water downward, are not accurately representing behavior, or are representing the excess flow (overflow) from a system. Design specifications should prevent putting contaminated runoff and excess water beyond that which will infiltrate within the given time frame. Any runoff containing toxic material or excess volume that cannot infiltrate should be diverted away from the infiltration system and reported as inflow to another treatment device. | |
− | + | {{:Median pollutant removal percentages for BMPs}} | |
==Limitations== | ==Limitations== | ||
Line 146: | Line 152: | ||
*Cold climate considerations for infiltration practices - See [http://stormwater.pca.state.mn.us/index.php/Cold_climate_impact_on_runoff_management#Infiltration], [http://stormwater.pca.state.mn.us/index.php/Cold_climate_impact_on_runoff_management#Infiltration_practices] | *Cold climate considerations for infiltration practices - See [http://stormwater.pca.state.mn.us/index.php/Cold_climate_impact_on_runoff_management#Infiltration], [http://stormwater.pca.state.mn.us/index.php/Cold_climate_impact_on_runoff_management#Infiltration_practices] | ||
− | [[Category:BMP overview | + | [[Category:Level 3 - Best management practices/Guidance and information/BMP overview]] |
− | |||
</noinclude> | </noinclude> |
Stormwater infiltration practices capture and temporarily store stormwater before allowing it to infiltrate into the soil. Infiltration practices are applicable to sites with naturally permeable soils and a suitable distance to the seasonally high groundwater table, bedrock or other impermeable layer. They may be used in residential and other urban settings where elevated runoff volumes, pollutant loads, and runoff temperatures are a concern. Stormwater runoff having high pollutant loads should receive a significant amount of pretreatment to protect the groundwater quality, particularly if soil infiltration rates are high (e.g. HSG A soils). Runoff from potential stormwater hotspots (PSH) should not be introduced to infiltration areas. Infiltration should be avoided in areas with contaminated soils or groundwater.
Design variants discussed on this page include the infiltration basin, the infiltration trench, the dry well and the underground infiltration system. To see overviews for other infiltration practices, see the following sections.
For discussions of how these practices differ or are similar to other infiltration practices, see Bioretention terminology and BMPs for stormwater infiltration.
The infiltration practices discussed on this page may be located at the end of the treatment train or they can be designed as offline configurations where the Water Quality Volume is diverted to the infiltration practice. In any case, the practice may be applied as part of a stormwater management system to achieve one or more of the following objectives:
One of the goals of this Manual is to facilitate understanding of and compliance with the General Stormwater Permit for Construction Activity (MN R100001), commonly called the Construction General Permit (CGP), which includes design and performance standards for permanent stormwater management systems. These standards must be applied in all projects in which at least 1 acre of new impervious area is being created, and the permit stipulates certain standards for various categories of stormwater management practices.
For regulatory purposes, infiltration practices fall under Infiltration systems in the permit. If used in combination with other practices, credit for combined stormwater treatment can be given. Due to the statewide prevalence of the MPCA permit, design guidance in this section is presented with the assumption that the permit does apply. Also, although it is expected that in many cases infiltration will be used in combination with other practices, standards are described for the case in which it is a stand alone practice.
The following terms are thus used in the text to distinguish various levels of stormwater pond design guidance.
REQUIRED: Indicates design standards stipulated by the MPCA Permit (or other consistently applicable regulations).
HIGHLY RECOMMENDED: Indicates design guidance that is extremely beneficial or necessary for proper functioning of the infiltration practice, but is not specifically required by the MPCA permit.
RECOMMENDED: Indicates design guidance that is helpful for infiltration performance but not critical to the design.
Of course, there are situations, particularly retrofit projects, in which an infiltration facility is constructed without being subject to the conditions of the MPCA permit. While compliance with the permit is not required in these cases, the standards it establishes can provide valuable design guidance to the user. It is also important to note that additional and potentially more stringent design requirements may apply for a particular infiltration facility, depending on where it is situated both jurisdictionally and within the surrounding landscape.
Applications for infiltration trenches, dry well, underground infiltration, and infiltration basins | |
Residential | Yes |
Commercial | Yes |
Ultra-urban | Yes except for infiltration basins, which are limited |
Industrial | Yes1 |
Highway/road | 2 |
Recreational | Yes |
1 Unless the infiltration practice is located in an industrial area with exposed significant materials or from vehicle fuelling and maintenance areas. Infiltration BMPs are PROHIBITED in these areas; 2 Yes for infiltration trench, limited for underground infiltration and infiltration basin, no for dry well |
Generally, infiltration should not be used to treat runoff from manufacturing or industrial sites or other areas with high pollutant concentrations unless correspondingly high levels of pretreatment are provided.
The BMP design restrictions for special watersheds table below provides guidance regarding the use of infiltration practices in areas upstream of special receiving waters.
Infiltration and filtration bmp1 design restrictions for special waters and watersheds. See also Sensitive waters and other receiving waters.
Link to this table
BMP Group | receiving water | ||||
---|---|---|---|---|---|
A Lakes | B Trout Waters | C Drinking Water2 | D Wetlands | E Impaired Waters | |
Infiltration | RECOMMENDED | RECOMMENDED | NOT RECOMMENDED if potential stormwater pollution sources evident | RECOMMENDED | RECOMMENDED unless target TMDL pollutant is a soluble nutrient or chloride |
Filtration | Some variations NOT RECOMMENDED due to poor phosphorus removal, combined with other treatments | RECOMMENDED | RECOMMENDED | ACCEPTABLE | RECOMMENDED for non-nutrient impairments |
1Filtration practices include green roofs, bmps with an underdrain, or other practices that do not infiltrate water and rely primarily on filtration for treatment.
2 Applies to groundwater drinking water source areas only; use the lakes category to define BMP design restrictions for surface water drinking supplies
Infiltration practices should remain effective water quality improvement systems for many years, even during winter conditions, if designed and constructed properly and it has been shown that hydraulic efficiency and infiltration rates can remain at levels used for design sizing. However, in cold climates, some special considerations are HIGHLY RECOMMENDED for surface systems to ensure sustained functionality and limit the damage freezing temperatures and snow and ice removal may cause.
One concern with infiltration in cold weather is the ice that forms both over the top of the practice and within the soil structure, which can completely stop infiltration. To limit the effect of this problem, it is HIGHLY RECOMMENDED that the facility be actively inspected to ensure that it is properly drawing down before it freezes in the late fall. Adequate drawdown can be determined using one of the several field assessment techniques such as those recommended by the University of Minnesota Extension (see section on Assessment). If it is determined that stormwater runoff is not infiltrating prior to hard freeze, the BMP should be placed offline for correction in the spring.
Even if the infiltration properties of an infiltration practice are marginal for snowmelt runoff during the period of deep frost in the winter, the storage available in the facility will provide water quality benefit if it is dry entering the melt season. Routing the first highly-soluble portions of snowmelt (first flush) to an infiltration facility provides the opportunity for soil treatment (such as filtration, adsorption, microbial activity) of these soluble pollutants. Again, however, flow originating in an industrial area, a high traffic area where large amounts of salt are added, or another PSH should be diverted away from infiltration systems if pretreatment features have not been properly designed to handle such an increase in loading. Proprietary, sub-grade infiltration systems provide an alternative to standard surface based systems. Essentially, these systems provide an insulated location for pre-treated snowmelt to be stored and slowly infiltrated, or simply filtered and drained away if groundwater sensitivity is an issue. The insulating value of these systems adds to their appeal as low land consumption alternatives to ponds and surface infiltration basins.
For all BMPs it is HIGHLY RECOMMENDED that snow and ice removal plans including predetermined locations for stockpiling be determined prior to or during the design process. Infiltration features cannot be used for significant snow storage areas as debris build-up, plant damage, and lower infiltration rates are likely to occur. Some snow storage unavoidable when BMPs are adjacent to areas where snow removal is required but it is critical that the property owner and snow and ice removal contractor have identified other areas for large scale snow storage.
Excessive deicing agents have the potential to create a hot spot in some locations that could lead to reduced infiltration rates or concentrations that exceed surface water or groundwater standards. Locations such as busy intersections on slopes, parking garage ramps or on walkways near the entrances of commercial buildings are likely to be heavily treated with deicing agents to avoid slip and falls or vehicle collisions. This should be taken into consideration when siting any infiltration BMP.
For bioinfiltration features, dry swales with check dams, and tree trenches, special considerations regarding snow and ice storage and plant maintenance are required. Plant selection is critical to ensure that the damaging effects of snow and ice removal do not severely impact plantings or seedings. Even a small amount of snow storage can break and uproot plants requiring additional maintenance in the spring. Woody trees and shrubs should be selected that can tolerate some salt spray from plowing operations.
The amount of stormwater volume infiltrated depends on the design variant selected. Smaller infiltration practices (e.g. infiltration trenches) should either be designed off-line using a flow diversion, or designed to safely pass large storm flows while still protecting the infiltration area. In limited cases (e.g. extremely permeable soils), these smaller infiltration practices can accommodate the channel protection volume, Vcp, in either an off- or on-line configuration.
In general, supplemental stormwater practices will be necessary to satisfy channel and flood protection requirements when smaller infiltration practices are used. However, these practices can help reduce detention requirements for a site through volume reduction.
Due to their size, the larger infiltration practices (e.g. infiltration basins and underground infiltration systems) have the potential to provide greater water quantity benefits. Surcharge storage above the practice bottom is available for detention. Outlet structures can be sized to partially or fully accommodate larger storm peak discharge control while allowing the volume below the outlet to infiltrate.
Infiltration practices can remove a wide variety of stormwater pollutants through chemical and bacterial degradation, sorption, and filtering. Surface water load reductions are also realized by virtue of the reduction in runoff volume.
There are few data available demonstrating the load reductions or outflow concentrations of larger-scale infiltration practices such as infiltration trenches. Similarly, few sampling programs collect infiltrating water that flows through an infiltration system.
For properly designed, operated, and maintained infiltration systems, all water routed into them should be “removed” from stormwater flow, resulting in 100 percent efficiency relative to volume and pollutant reduction. For this reason, any infiltration BMP performance table should show all 100 percent entries for that portion of stormwater entering the infiltration system. This logic assumes that stormwater is the beneficiary of any infiltration system, but ignores the fact that pollution, if any remains after the internal workings of the infiltration BMP itself (see later discussion in this section), is being transferred into the shallow groundwater system. See Surface water and groundwater quality impacts from stormwater infiltration.
Properly designed infiltration systems discussed later in this section will accommodate a design volume based on the required water quality volume. Excess water must be bypassed and diverted to another BMP so that the design infiltration occurs within 48 hours if under state regulation, or generally within 72 hours under certain local and watershed regulations. In no case should the bypassed volume be included in the pollutant removal calculation.
Data that are reported in performance literature for infiltration systems, unless reporting 100 percent effectiveness for surface water or documenting outflow water downward, are not accurately representing behavior, or are representing the excess flow (overflow) from a system. Design specifications should prevent putting contaminated runoff and excess water beyond that which will infiltrate within the given time frame. Any runoff containing toxic material or excess volume that cannot infiltrate should be diverted away from the infiltration system and reported as inflow to another treatment device.
Median pollutant removal percentages for several stormwater BMPs. Sources. More detailed information and ranges of values can be found in other locations in this manual, as indicated in the table. NSD - not sufficient data. NOTE: Some filtration bmps, such as biofiltration, provide some infiltration. The values for filtration practices in this table are for filtered water.
Link to this table
Practice | TSS | TP | PP | DP | TN | Metals1 | Bacteria | Hydrocarbons |
---|---|---|---|---|---|---|---|---|
Infiltration2 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
Biofiltration and Tree trench/tree box with underdrain | 80 | link to table | link to table | link to table | 50 | 35 | 95 | 80 |
Sand filter | 85 | 50 | 85 | 0 | 35 | 80 | 50 | 80 |
Iron enhanced sand filter | 85 | 65 or 746 | 85 | 40 or 606 | 35 | 80 | 50 | 80 |
Dry swale (no check dams) | 68 | link to table | link to table | link to table | 35 | 80 | 0 | 80 |
Wet swale (no check dams) | 35 | 0 | 0 | 0 | 15 | 35 | 35 | NSD |
Constructed wet ponds4, 5 | 84 | 50 or 685 | 84 | 8 or 485 | 30 | 60 | 70 | 80 |
Constructed wetlands | 73 | 38 | 69 | 0 | 30 | 60 | 70 | 80 |
Permeable pavement (with underdrain) | 74 | 41 | 74 | 0 | NSD | NSD | NSD | NSD |
Green roofs | 85 | 0 | 0 | 0 | NSD | NSD | NSD | NSD |
Vegetated (grass) filter | 68 | 0 | 0 | 0 | NSD | NSD | NSD | NSD |
Harvest and reuse | Removal is 100% for captured water that is infiltrated. For water captured and routed to another practice, use the removal values for that practice. |
TSS=Total suspended solids, TP=Total phosphorus, PP=Particulate phosphorus, DP=Dissolved phosphorus, TN=Total nitrogen
1Data for metals is based on the average of data for zinc and copper
2BMPs designed to infiltrate stormwater runoff, such as infiltration basin/trench, bioinfiltration, permeable pavement with no underdrain, tree trenches with no underdrain, and BMPs with raised underdrains.
3Pollutant removal is 100 percent for the volume infiltrated, 0 for water bypassing the BMP. For filtered water, see values for other BMPs in the table.
4Dry ponds do not receive credit for volume or pollutant removal
5Removal is for Design Level 2. If an iron-enhanced pond bench is included, an additional 40 percent credit is given for dissolved phosphorus. Use the lower values if no iron bench exists and the higher value if an iron bench exists.
6Lower values are for Tier 1 design. Higher values are for Tier 2 design.
The following general limitations should be recognized when considering installation of infiltration practices.
Please note that even though there are potential pollution and physical clogging problems with infiltration, it is one of the most important elements in the stormwater runoff treatment train. Fear of the limitations should not prevent well designed systems from being used.
As noted in various sections, discussion of BMP selection, the benefits associated with infiltration BMPs should only be accrued based on the amount of water actually passing through the BMP. Excess runoff beyond that designed for the BMP should not be routed through the system because of the potential for hydraulic and particulate over-loading, both of which will adversely impact the life and operation of the BMP. For example, an infiltration device designed to treat the first 0.5 inch of runoff from a fully impervious surface will catch about 30 percent of the volume of runoff in the Twin Cities. This means that 70 percent of the runoff volume should be routed around the filtration system and will not be subject to the removals reflected in the above tables. Attributing removal to all runoff just because a BMP is in place in a drainage system is not a legitimate claim.