[[File:Pervious concrete cross section.jpg|thumb|300 px|alt=This schematic illustrates typical pervious concrete cross section and basic components of a pervious concrete system|<font size=3>Schematic illustrating typical pervious concrete cross section and basic components of a pervious concrete system.</font size>]] | [[File:Pervious concrete cross section.jpg|thumb|300 px|alt=This schematic illustrates typical pervious concrete cross section and basic components of a pervious concrete system|<font size=3>Schematic illustrating typical pervious concrete cross section and basic components of a pervious concrete system.</font size>]] | ||
Line 26: | Line 27: | ||
:Soil surveys and HSG classifications provide a general estimate of the soil's infiltration rate. Soil infiltration rates can also be estimated from soil classifications per [http://www.astm.org/Standard/index.shtml ASTM] D2487. However, it is best to determine rates using on-site infiltration testing per ASTM D3385 Standard Test Method for Infiltration Rate of Soils in Field Using Double-Ring Infiltrometer, D5093 Standard Test Method for Field Measurement of Infiltration Rate Using Double-Ring Infiltrometer with Sealed-Inner Ring or other available methods. The median rate determined from in-situ measurements should be reduced by a factor of 2.5 and this reduced value used in design calculations. This reduction accounts for incidental compaction during construction and sedimentation of the subgrade over time. | :Soil surveys and HSG classifications provide a general estimate of the soil's infiltration rate. Soil infiltration rates can also be estimated from soil classifications per [http://www.astm.org/Standard/index.shtml ASTM] D2487. However, it is best to determine rates using on-site infiltration testing per ASTM D3385 Standard Test Method for Infiltration Rate of Soils in Field Using Double-Ring Infiltrometer, D5093 Standard Test Method for Field Measurement of Infiltration Rate Using Double-Ring Infiltrometer with Sealed-Inner Ring or other available methods. The median rate determined from in-situ measurements should be reduced by a factor of 2.5 and this reduced value used in design calculations. This reduction accounts for incidental compaction during construction and sedimentation of the subgrade over time. | ||
− | {{alert|The safety factor of 2.5 is greater than a factor of 2 recommended in most guidance for permeable pavement | + | {{alert|The safety factor of 2.5 is greater than a factor of 2 recommended in most guidance for permeable pavement. This manual utilizes recommended soil infiltration rates for hydrologic soil groups (see [http://stormwater.pca.state.mn.us/index.php/Design_infiltration_rates]). These are not as conservative as infiltration rates based on the [https://www.pca.state.mn.us/sites/default/files/p-gen3-12d.pdf Unified Soil Classification System], particularly for finer textured soils. We therefore recommended the more conservative value of 2.5|alert-info}} |
:In most cases, permeable pavement should not be situated above fill soils. Designs in compacted fill soils may require an impermeable liner and an underdrain. Permeable pavements should only be placed on fill soils when laboratory tests indicate the compacted fill will be stable when saturated and that slope stability of deep fills has been verified by a geotechnical engineer. | :In most cases, permeable pavement should not be situated above fill soils. Designs in compacted fill soils may require an impermeable liner and an underdrain. Permeable pavements should only be placed on fill soils when laboratory tests indicate the compacted fill will be stable when saturated and that slope stability of deep fills has been verified by a geotechnical engineer. | ||
Line 34: | Line 35: | ||
*Contributing drainage area – Permeable pavements sometimes capture runoff from adjacent areas, pavements, and roofs. Runoff from permeable areas is not recommended due to potential clogging of the permeable pavement. The at-grade contributing drainage area into permeable pavement should generally not exceed twice the surface area of the permeable pavement. This guideline helps reduce the rate of surface sedimentation. The 2:1 ratio can be increased to no greater than 5:1 if at least one of these conditions exists: | *Contributing drainage area – Permeable pavements sometimes capture runoff from adjacent areas, pavements, and roofs. Runoff from permeable areas is not recommended due to potential clogging of the permeable pavement. The at-grade contributing drainage area into permeable pavement should generally not exceed twice the surface area of the permeable pavement. This guideline helps reduce the rate of surface sedimentation. The 2:1 ratio can be increased to no greater than 5:1 if at least one of these conditions exists: | ||
**permeable pavement is receiving runoff from roofs as it tends to be very low in sediment; or | **permeable pavement is receiving runoff from roofs as it tends to be very low in sediment; or | ||
− | **runoff from adjacent impervious surfaces remains unburdened with sediment due to effective | + | **runoff from adjacent impervious surfaces remains unburdened with sediment due to effective pretreatment prior to entering the permeable pavement. |
For more information on contributing area, see [[Contributing drainage area to stormwater BMPs]]. | For more information on contributing area, see [[Contributing drainage area to stormwater BMPs]]. | ||
Line 52: | Line 53: | ||
*Minimum depth to [[Glossary#S|seasonal high water table]] – A high groundwater table may cause seepage into the bottom of permeable pavement and prevent complete drainage. Also, soil acts as a filter for pollutants between the bottom of the pavement base and the water table. Therefore, a minimum vertical separation of 3 feet is required between the bottom of the permeable pavement reservoir layer and the seasonal high groundwater table. For systems with impermeable liners, a minimum of one foot clearance is Highly recommended between the liner and the seasonal high water table. | *Minimum depth to [[Glossary#S|seasonal high water table]] – A high groundwater table may cause seepage into the bottom of permeable pavement and prevent complete drainage. Also, soil acts as a filter for pollutants between the bottom of the pavement base and the water table. Therefore, a minimum vertical separation of 3 feet is required between the bottom of the permeable pavement reservoir layer and the seasonal high groundwater table. For systems with impermeable liners, a minimum of one foot clearance is Highly recommended between the liner and the seasonal high water table. | ||
− | *Setbacks – To avoid harmful seepage, permeable pavement should not be hydraulically connected to building foundations unless an impermeable liner is placed against the foundation or basement wall. Even under these circumstances, great care should be taken to avoid creating a wet basement problem. If there is no liner, the permeable pavement base should be 10 feet or greater from structures (EPA recommends a minimum setback from building foundations of 10 feet down-gradient and 100 feet up-gradient. See EPA factsheet “Storm Water Technology Fact Sheet: Porous Pavement,” [ | + | *Setbacks – To avoid harmful seepage, permeable pavement should not be hydraulically connected to building foundations unless an impermeable liner is placed against the foundation or basement wall. Even under these circumstances, great care should be taken to avoid creating a wet basement problem. If there is no liner, the permeable pavement base should be 10 feet or greater from structures (EPA recommends a minimum setback from building foundations of 10 feet down-gradient and 100 feet up-gradient. See EPA factsheet “Storm Water Technology Fact Sheet: Porous Pavement,” [https://nepis.epa.gov/Exe/ZyNET.exe/91018M1N.TXT?ZyActionD=ZyDocument&Client=EPA&Index=1995+Thru+1999&Docs=&Query=&Time=&EndTime=&SearchMethod=1&TocRestrict=n&Toc=&TocEntry=&QField=&QFieldYear=&QFieldMonth=&QFieldDay=&IntQFieldOp=0&ExtQFieldOp=0&XmlQuery=&File=D%3A%5Czyfiles%5CIndex%20Data%5C95thru99%5CTxt%5C00000032%5C91018M1N.txt&User=ANONYMOUS&Password=anonymous&SortMethod=h%7C-&MaximumDocuments=1&FuzzyDegree=0&ImageQuality=r75g8/r75g8/x150y150g16/i425&Display=hpfr&DefSeekPage=x&SearchBack=ZyActionL&Back=ZyActionS&BackDesc=Results%20page&MaximumPages=1&ZyEntry=1&SeekPage=x&ZyPURL EPA 832-F-99-023]). Again, it is the designer’s responsibility to avoid creating a wet basement problem. Likewise, permeable pavement bases should be hydraulically separated from adjacent road bases. |
:Permeable pavements without underdrains infiltrate stormwater and should follow requirements for wellhead protection (EPA recommends a minimum setback of 100 feet from water supply wells). Underground utility lines are best located away from permeable pavement bases. However, if they need to penetrate the base, consideration should be given to waterproofing (depending on the utility) or possible encasement using low-strength flowable concrete fill. Setbacks can be reduced at the discretion of the local authority for designs that use underdrains and/or liners. | :Permeable pavements without underdrains infiltrate stormwater and should follow requirements for wellhead protection (EPA recommends a minimum setback of 100 feet from water supply wells). Underground utility lines are best located away from permeable pavement bases. However, if they need to penetrate the base, consideration should be given to waterproofing (depending on the utility) or possible encasement using low-strength flowable concrete fill. Setbacks can be reduced at the discretion of the local authority for designs that use underdrains and/or liners. | ||
Line 74: | Line 75: | ||
===Structural design=== | ===Structural design=== | ||
− | The structural design process for supporting vehicles varies according to the type of pavement selected. The pervious concrete industry is in the process of developing ASTM test methods for characterizing compressive or flexural strengths of pervious concrete. These tests are needed to model fatigue under loads. As an interim step, fatigue equations published by the American Concrete Pavement Association ([http://www.pavement.com/ ACPA] 2010) assume such inputs to be comparable in nature (but not magnitude) to those used for conventional concrete pavements. The ACPA design method should be consulted for further information as well as pervious concrete industry software. General guidelines for pervious concrete surface thickness are published by the National Ready Mix Concrete Association [http://www.nrmca.org/ NRMCA] and the | + | The structural design process for supporting vehicles varies according to the type of pavement selected. The pervious concrete industry is in the process of developing ASTM test methods for characterizing compressive or flexural strengths of pervious concrete. These tests are needed to model fatigue under loads. As an interim step, fatigue equations published by the American Concrete Pavement Association ([http://www.pavement.com/ ACPA] 2010) assume such inputs to be comparable in nature (but not magnitude) to those used for conventional concrete pavements. The ACPA design method should be consulted for further information as well as pervious concrete industry software. General guidelines for pervious concrete surface thickness are published by the National Ready Mix Concrete Association [http://www.nrmca.org/ NRMCA] and the [https://www.cement.org/ Portland Cement Association]. |
<p>Porous asphalt ([[References for permeable pavement|Hansen 2008]]) and permeable interlocking pavements ([[References for permeable pavement|Smith 2011]]) use flexible pavement design methods adopted from the 1993 AASHTO ''Guide for Design of Pavement Structures'' ([[References for permeable pavement|AASHTO 1993]]). In addition, MnDOT design methods, approved mechanistic principles, and manufacturer’s specific recommendations should be consulted.</p> | <p>Porous asphalt ([[References for permeable pavement|Hansen 2008]]) and permeable interlocking pavements ([[References for permeable pavement|Smith 2011]]) use flexible pavement design methods adopted from the 1993 AASHTO ''Guide for Design of Pavement Structures'' ([[References for permeable pavement|AASHTO 1993]]). In addition, MnDOT design methods, approved mechanistic principles, and manufacturer’s specific recommendations should be consulted.</p> | ||
<p>There has been limited research on full-scale testing of the structural behavior of open-graded bases used under permeable pavements to better characterizing relationships between loads and deformation. Therefore, conservative values (i.e., AASHTO layer coefficients) should be assumed for open-graded base and subbase aggregates in permeable pavement design.</p> | <p>There has been limited research on full-scale testing of the structural behavior of open-graded bases used under permeable pavements to better characterizing relationships between loads and deformation. Therefore, conservative values (i.e., AASHTO layer coefficients) should be assumed for open-graded base and subbase aggregates in permeable pavement design.</p> | ||
Line 90: | Line 91: | ||
These options are typically used in combination. Pedestrian applications can be placed on lower strength soils than those noted.</p> | These options are typically used in combination. Pedestrian applications can be placed on lower strength soils than those noted.</p> | ||
<p>Pedestrian applications can be placed on lower strength soils than those noted.</p> | <p>Pedestrian applications can be placed on lower strength soils than those noted.</p> | ||
− | |||
<!--===Hydrologic Sizing=== | <!--===Hydrologic Sizing=== | ||
The soil subgrade infiltration rate typically is far lower than the flow rate through the pavement, so some reservoir storage will usually be required to maximize the stormwater benefit of permeable pavement. Often times permeable pavement is designed to store a given design storm. For instance, Minnesota’s Minimal Impact Design Standards ([[Performance goals for new development, re-development and linear projects|MIDS]]) require a performance goal of managing 1.1 inches of runoff from the tributary impervious surfaces. For this design standard, the volume of the reservoir layer will be required to store 1.1 inches of stormwater runoff entering from the impervious area plus rainfall directly into the permeable pavement itself. | The soil subgrade infiltration rate typically is far lower than the flow rate through the pavement, so some reservoir storage will usually be required to maximize the stormwater benefit of permeable pavement. Often times permeable pavement is designed to store a given design storm. For instance, Minnesota’s Minimal Impact Design Standards ([[Performance goals for new development, re-development and linear projects|MIDS]]) require a performance goal of managing 1.1 inches of runoff from the tributary impervious surfaces. For this design standard, the volume of the reservoir layer will be required to store 1.1 inches of stormwater runoff entering from the impervious area plus rainfall directly into the permeable pavement itself. | ||
Line 139: | Line 139: | ||
Once the outflow rate through each underdrain has been approximated, the depth of the base/subbase needed to store the design storm can be determined by | Once the outflow rate through each underdrain has been approximated, the depth of the base/subbase needed to store the design storm can be determined by | ||
− | <math>d_p = | + | <math>d_p = ((0.95 * RP) – (i/2)t_f)) / n</math> |
where | where | ||
− | : | + | :0.95 is the runoff coefficient for impermeable surfaces; |
:''d<sub>p</sub>'' = the depth of the reservoir layer (feet); | :''d<sub>p</sub>'' = the depth of the reservoir layer (feet); | ||
− | + | :''R'' = ''A''<sub>''c''</sub>/''A''<sub>''p''</sub> The ratio of the contributing drainage area (''A''<sub>''c''</sub>, including the permeable paving surface), to the permeable pavement surface area (''A''<sub>''p''</sub>); | |
− | :''R'' = ''A''<sub>''c''</sub>/''A''<sub>''p''</sub> The ratio of the contributing drainage area (''A''<sub>''c''</sub>, | ||
:''t<sub>f</sub>'' = the time to fill the reservoir layer (day) – typically 2 hours or 0.083 day; | :''t<sub>f</sub>'' = the time to fill the reservoir layer (day) – typically 2 hours or 0.083 day; | ||
− | :''P'' = the rainfall depth for the | + | :''P'' = the rainfall depth for the design storm (feet); |
− | :''i'' = field-verified infiltration rate (ft/day) | + | :''i'' = field-verified infiltration rate (ft/day); and |
− | |||
:''n'' = porosity (cubic feet/cubic feet) | :''n'' = porosity (cubic feet/cubic feet) | ||
<!--:''V<sub>r</sub>'' = the void ratio for the reservoir layer (typically 0.4).--> | <!--:''V<sub>r</sub>'' = the void ratio for the reservoir layer (typically 0.4).--> | ||
Line 155: | Line 153: | ||
To estimate the number of underdrain pipes (N), take the dimension of the parking lot in the direction the pipes are to be placed and divide by the desired spacing between pipes – round down to the nearest whole number. | To estimate the number of underdrain pipes (N), take the dimension of the parking lot in the direction the pipes are to be placed and divide by the desired spacing between pipes – round down to the nearest whole number. | ||
− | + | With full infiltration systems, the maximum allowable drain time (''t''<sub>''d''</sub>) needs to be calculated to make sure the stored water within the base/subbase does not take too long to infiltrate into the soil subgrade. | |
+ | |||
+ | <math>t{d} = (d_pn) / (0.5i) </math> | ||
− | + | The total storage in the permeable pavement system, V<sub>s</sub>, is given by | |
− | <math> | + | <math> V_{s} = A_{p} (d_pn + 0.5it_{f}) </math> |
where | where | ||
− | :'' | + | :''A<sub>p</sub>'' is the surface area of the permeable pavement (ft<sup>2</sup>). |
− | |||
− | |||
− | |||
− | |||
− | |||
− | + | When calculating the storage volume for compliance with the Construction Stormwater Permit, only the instantaneous storage volume is considered | |
− | + | <math> V_{s} = A_{p} (d_pn) </math> | |
− | |||
− | <math> | ||
− | |||
− | |||
− | |||
− | |||
Permeable pavement can also be designed to augment detention storage needed for channel protection and/or flood control. The designer can model various approaches by factoring in storage within the base/subbase, expected infiltration and any outlet structures used as part of the design. | Permeable pavement can also be designed to augment detention storage needed for channel protection and/or flood control. The designer can model various approaches by factoring in storage within the base/subbase, expected infiltration and any outlet structures used as part of the design. | ||
Line 240: | Line 229: | ||
'''Karst:''' It is ''HIGHLY RECOMMENDED'' that infiltration practices not be used in active karst formations without adequate geotechnical testing. | '''Karst:''' It is ''HIGHLY RECOMMENDED'' that infiltration practices not be used in active karst formations without adequate geotechnical testing. | ||
− | '''Wellhead Protection Areas''': It is ''HIGHLY RECOMMENDED'' to review the [ | + | '''Wellhead Protection Areas''': It is ''HIGHLY RECOMMENDED'' to review the [https://www.health.state.mn.us/communities/environment/water/swp/index.htm Minnesota Department of Health guidance] on stormwater infiltration in Wellhead Protection Areas. |
===Pretreatment=== | ===Pretreatment=== | ||
Line 280: | Line 269: | ||
==Design checklists== | ==Design checklists== | ||
− | Design checklists have not been developed for the Minnesota Stormwater Manual | + | Design checklists have not been developed for the Minnesota Stormwater Manual. Below are links to checklists developed by other organizations. |
− | *[ | + | *[https://secureservercdn.net/166.62.110.232/e6d.7d8.myftpupload.com/wp-content/uploads/2020/07/Permeable-Pavement-Check-List-July2019.pdf Iowa Stormwater Education Partnership, Permeable Paver Design Review Checklist] |
*[https://www.slideshare.net/Cartegraph/permeable-pavement-check-list Cartegraph, Permeable Pavement Design Review checklist] | *[https://www.slideshare.net/Cartegraph/permeable-pavement-check-list Cartegraph, Permeable Pavement Design Review checklist] | ||
<noinclude> | <noinclude> | ||
+ | |||
==Related articles== | ==Related articles== | ||
*[[Overview for permeable pavement]] | *[[Overview for permeable pavement]] | ||
Line 311: | Line 301: | ||
[https://stormwater.pca.state.mn.us/index.php?title=Permeable_pavement Permeable pavement main page] | [https://stormwater.pca.state.mn.us/index.php?title=Permeable_pavement Permeable pavement main page] | ||
− | [[ | + | [[Category:Level 3 - Best management practices/Specifications and details/Design criteria]] |
− | |||
</noinclude> | </noinclude> |
This section provides information on design considerations, criteria and specifications for permeable pavement. Base/subbase thickness is determined for water storage using hydrologic sizing and/or dynamic modeling over time. Base/subbases thickness for supporting traffic is determined using structural design methods. The thicker of the two resulting designs is employed.
Implicit in the design guidance is the fact that many design elements of infiltration and filtration systems can minimize the maintenance burden and maintain pollutant removal efficiency. Key examples include
For more information on design information for individual infiltration and filtration practices, link here.
Permeable pavement is subject to the following design considerations, including benefits and constraints.
For more information on contributing area, see Contributing drainage area to stormwater BMPs.
Base/subbase thickness is determined for support traffic using structural design methods and for water storage using hydrologic sizing and/or dynamic modeling over time. The thicker of the two resulting designs is used.
The structural design process for supporting vehicles varies according to the type of pavement selected. The pervious concrete industry is in the process of developing ASTM test methods for characterizing compressive or flexural strengths of pervious concrete. These tests are needed to model fatigue under loads. As an interim step, fatigue equations published by the American Concrete Pavement Association (ACPA 2010) assume such inputs to be comparable in nature (but not magnitude) to those used for conventional concrete pavements. The ACPA design method should be consulted for further information as well as pervious concrete industry software. General guidelines for pervious concrete surface thickness are published by the National Ready Mix Concrete Association NRMCA and the Portland Cement Association.
Porous asphalt (Hansen 2008) and permeable interlocking pavements (Smith 2011) use flexible pavement design methods adopted from the 1993 AASHTO Guide for Design of Pavement Structures (AASHTO 1993). In addition, MnDOT design methods, approved mechanistic principles, and manufacturer’s specific recommendations should be consulted.
There has been limited research on full-scale testing of the structural behavior of open-graded bases used under permeable pavements to better characterizing relationships between loads and deformation. Therefore, conservative values (i.e., AASHTO layer coefficients) should be assumed for open-graded base and subbase aggregates in permeable pavement design.
Regardless of type of permeable pavement, structural design methods consider the following in determining surface and base thicknesses to support vehicular traffic:
Soil stability under traffic should be carefully reviewed for each application by a qualified geotechnical or civil engineer and lowest anticipated soil strength or stiffness values under saturated conditions used for design. Structural design for vehicular applications should generally be on soil subgrades with a CBR (96-hour soaked per ASTM D 1883 or AASHTO T 193) of 4 percent, or a minimum R-value = 9 per ASTM D 2844 or AASHTO T-190, or a minimum Mr of 6,500 pounds per square inch (45 Mega Pascals) per AASHTO T-307. Soils with lower strengths typically require thickened permeable bases or those using cement or asphalt stabilized open-graded aggregates per Mn/DOT Pavement Manual, Section 3-3.01.02 Treated Base.
Soil compaction required to achieve these soil strengths will reduce the infiltration rate of the soil. Therefore, the permeability or infiltration rate of soil should be assessed at the density required to achieve one of these values. If soils under vehicular traffic have lower strengths than those noted above, or are expansive when wet, there are several options, including
These options are typically used in combination. Pedestrian applications can be placed on lower strength soils than those noted.
Pedestrian applications can be placed on lower strength soils than those noted.
If the depth of the base/subbase for the full infiltration system is excessive, because, as an example, the design subgrade soil infiltration rate is not adequate to remove the water from the design storm within the designated period of time, then the design should include underdrains. The following procedure is for sizing the base/subbase for partial infiltration designs (i.e. contains underdrains).
The outflow rate from underdrain(s) can be approximated by
\(q_u = k m\)
where
This equation is based on Darcy’s Law, which summarizes several properties that groundwater exhibits while flowing in aquifers. Although the hydraulic conductivity (measure of the ease with which water can move through pore spaces of a material) of the aggregate subbase is very high (approximately 17,000 feet per day or 8,500 inches per hour), the discharge rate through underdrains is limited by the cross sectional area of the pipe. As the storage volume above/around the underdrain(s) decreases (i.e., the hydraulic head or water pressure decreases), the base/subbase and in turn the underdrain(s) will drain increasingly slower. To account for this change in flow conditions within the subbase and underdrain(s) over time, a very conservative coefficient of permeability (k) of 100 feet per day per pipe can be used to approximate the average underdrain outflow rate.
Once the outflow rate through each underdrain has been approximated, the depth of the base/subbase needed to store the design storm can be determined by
\(d_p = ((0.95 * RP) – (i/2)t_f)) / n\)
where
To estimate the number of underdrain pipes (N), take the dimension of the parking lot in the direction the pipes are to be placed and divide by the desired spacing between pipes – round down to the nearest whole number.
With full infiltration systems, the maximum allowable drain time (td) needs to be calculated to make sure the stored water within the base/subbase does not take too long to infiltrate into the soil subgrade.
\(t{d} = (d_pn) / (0.5i) \)
The total storage in the permeable pavement system, Vs, is given by
\( V_{s} = A_{p} (d_pn + 0.5it_{f}) \)
where
When calculating the storage volume for compliance with the Construction Stormwater Permit, only the instantaneous storage volume is considered
\( V_{s} = A_{p} (d_pn) \)
Permeable pavement can also be designed to augment detention storage needed for channel protection and/or flood control. The designer can model various approaches by factoring in storage within the base/subbase, expected infiltration and any outlet structures used as part of the design.
Once runoff passes through the surface of the permeable pavement system, designers should calculate outflow pathways to handle subsurface flows. Subsurface flows can be regulated using underdrains, the volume of storage in the reservoir layer, the bed slope of the reservoir layer, and/or a control structure at the outlet.
Permeable pavements can be designed to reduce nutrient loadings to the ground or surface waters. The design needs to be specifically designed to capture phosphorus. The permeable pavement system can also be designed to capture nitrogen, although it is important to note that nitrogen and phosphorus each require specific designs to facilitate their removal from stormwater. The following paragraphs describe the design characteristics necessary for the removal of phosphorus and nitrogen.
A study by (Bean, 2007a) showed higher nitrate concentrations in the exfiltrate compared to the infiltrate. Nitrogen reduction capabilities of permeable pavement can be enhanced in partial infiltration designs that detain water in the base/subbase for over 24 hours. This time is required to ensure complete de-nitrification occurs.
PICP can use specially coated aggregates in the joints and bedding and all systems can use them in the base to reduce phosphorous. Coated aggregates (sometimes called “engineered aggregates”) have an effective life of seven to ten years and target the removal of dissolved phosphorous, according to manufacturer’s literature.
A filter layer made of sand or fine aggregate placed under or sandwiched within permeable pavement bases are occasionally used as a means to reduce nutrients. This layer can be enhanced with iron filings for phosphorous reduction (Erickson 2010). Their effectiveness, initial cost, reduction in flow rates, and maintenance costs should be weighed against other design options for nutrient reductions. Sand filters will incur additional construction expense and this can be reduced by placing sand filters under the subbase at the down slope end of a permeable pavement. The disadvantage of sand filters is that they will eventually require removal and restoration if continued phosphorus reduction credit is desired. Concentrating their location in the down slope areas of the site can help reduce future maintenance costs and site disruptions.
A second approach useful for nutrient and TSS reduction can occur on sloping sites by creating intermittent berms in the soil subgrade. These enable settlement of suspended solids and encourage de-nitrification if appropriately designed. A third alternative is using a “treatment train” approach where a permeable pavement initially filters runoff and the remaining water outflows to bioswales or rain gardens adjacent to the pavement for additional processing and nutrient reduction. There may be additional BMPs used to remove nutrients as the water moves through the watershed.
Prior to infiltration testing, soil borings should be taken with an auger to assess the consistency of the soil type and horizons. Guidance for conducting infiltration tests and for determining the number of borings can be found here.
Permeable pavement designs should include methods to convey larger storms (e.g., 2-year, 10-year) to the storm drain system. The following is a list of methods that accomplish this.
The reservoir below the permeable pavement surface should be composed of clean, washed crushed stone aggregate and thickness sized for both the storm event to be stored and the structural requirements of the expected traffic loading. The recommended minimum void ratio should be 40 percent per ASTM C29. Reservoir base layers for pervious concrete are typically washed AASHTO No. 57 stone and those for porous asphalt are AASHTO No. 2, 3, or 5. PICP uses AASHTO No. 2, 3, or 4 stone.
If exposed to vehicular loads, all crushed stone should be Minnesota Department of Transportation (MnDOT) Class A or B coarse aggregate, minimum 80 percent crushed, typically granite, basalt, gneiss, trap rock, diabase, gabbro, or similar material. The maximum Los Angeles Rattler Loss should be 35 percent per AASHTO T-96 and no greater loss than 10 percent per AASHTO T-104 Magnesium Sulfate Soundness Test on the non-igneous portions and as modified by the MnDOT Laboratory Manual (MNDOT 2005). Limestone aggregates not meeting these requirements are not recommended in vehicular applications. Class C and D aggregates may be used in areas subject only to pedestrian traffic.
Underdrains install quickly when placed on or in the soil subgrade, surrounded by stone base materials. The outflow portion at the end is not perforated and is raised to a designed height that allows for some water detention prior to outflow. Placement at this elevation also protects the pipe with aggregate during base compaction. For permeable pavement bases/subbases using 2 or 3 inch maximum size aggregates, underdrain pipes with them should be surrounded with at least 4 inches of ASTM No. 57 (maximum 1 inch size aggregate) to protect the pipes during compaction. An underdrain(s) can also be installed and capped at a downstream structure as an option for future use if maintenance observations indicate a reduction in the soil permeability.
Proper maintenance of permeable pavement is crucial for ensuring its longevity and functionality. Some portions of the maintenance plan require planning during the design stages. These items are noted below.
The following design elements apply to permeable pavement.
Local authorities may require greater separation depths.
It is HIGHLY RECOMMENDED that infiltration practices not be hydraulically connected to structure foundations or pavement, to avoid seepage and frost heave concerns, respectively. If groundwater contamination is a concern, it is RECOMMENDED that groundwater mapping be conducted to determine possible connections to adjacent groundwater wells.
Required and recommended minimum vertical and horizontal separation distances. This represents the minimum distance from the infiltration practice to the structure of concern. If the structure is above-ground, the distance is measured from the edge of the BMP to the structure. If the structure is underground, the vertical separation distance represents the distance from the point of infiltration through the bottom of the system to the structure, while the horizontal separation (often called setback) distance is the shortest distance from the edge of the system to the structure.
Link to this table
Structure | Distance (feet) | Requirement or recommendation | Note(s) | |
---|---|---|---|---|
Vertical | Saturated soil | 3 | Requirement1 | |
Bedrock | 3 | Requirement1 | ||
Horizontal | Public supply well | 100 for sensitive wells; 50 for others3 | Requirement | |
Building/structure/property line2 | 10 | Recommended | ||
Surface water | none unless local requirements exist | If nearby stream is impaired for chloride, see [2] | ||
Septic system | 35 | Recommended | ||
Contaminated soil/groundwater | No specific distance. Infiltration must not mobilize contaminants. | |||
Slope | 200 | Recommended | from toe of slope >= 20% | |
Karst | 1000 up-gradient 100 down-gradient | Requirement1 | active karst |
1 Required under the Construction Stormwater General Permit
2 Minimum with slopes directed away from the building
3If treating an average of 10,000 gallons per day; otherwise separation distance is 300 feet
Karst: It is HIGHLY RECOMMENDED that infiltration practices not be used in active karst formations without adequate geotechnical testing.
Wellhead Protection Areas: It is HIGHLY RECOMMENDED to review the Minnesota Department of Health guidance on stormwater infiltration in Wellhead Protection Areas.
It is HIGHLY RECOMMENDED that the following pretreatment sizing guidelines be followed:
It is HIGHLY RECOMMENDED that pretreatment practices be designed such that exit velocities from the pretreatment systems are non-erosive (less than 3 feet per second) and flows are evenly distributed across the width of the practice (e.g., by using a level spreader).
The depth of an infiltration practice is a function of the maximum drawdown time and the design infiltration rate.
Permeable pavement material specifications vary according to the specific pavement product selected. The following table describes general material specifications for the components installed beneath the permeable pavement. Note that the size of stone materials used in the reservoir and filter layers differ depending whether the system is pervious concrete, porous asphalt or permeable interlocking concrete pavement.
Summary of specifications for materials under the pavement surface. For more information, see the footnote (1). Reference or links to any specific commercial product, process, or service by trade name, trademark, service mark, manufacturer, or otherwise does not constitute or imply endorsement, recommendation, or favoring by the Minnesota Pollution Control Agency.
Link to this table
Bedding/choker layer |
|
Washed free of fines |
Reservoir Layer |
|
Stone layer thickness based on the pavement structural and hydraulic requirements. Stonewashed and free of fines. Recommended minimum void ratio = 0.4. |
Underdrain (optional) | Use 4 to 6 inch diameter perforated PVC (AASHTO M-252) pipe or corrugated polyethylene pipe. Perforated pipe installed for the full length of the permeable pavement cell, and non-perforated pipe, as needed,connected to storm drainage system. | |
Filter Layer (optional) | Sand filter layeris separated from base above and native soils with geotextile. Sand layer typically ASTM C33 gradation, 6 to 12 inches thick. | The Filter Layer is REQUIRED if using the permeable pavement system to meet permit requirements. The sand layer may require a choker layer on surface to provide transition to base layerstone. |
Geotextile(optional) | Comply with AASHTO M-288 Standard Specification for Geotextile Specification for Highway Applications, drainage and separation applications, Class I or II. Porous asphalt industry recommends non-woven geotextile. | |
Impermeable Liner | Use a minimum 30mil PVC liner covered by 12 ounce/square yard non-woven geotextile. EPDM and HDPE liner material is also acceptable. | |
Observation Well | Use a perforated 4 to 6 inch vertical PVC pipe (AASHTO M-252) with a lockable cap, installedflush with the surface (or under pavers). |
1for additional information on materials referenced in this table (e.g. stone dimensions), see the following links:
A general comparison of different permeable pavements is provided in the following table. Designers should consult industry association and manufacturer’s technical specifications for specific criteria and guidance.
This table shows summarizes specifications for permeable pavement.
Link to this table.
Permeable Pavers | Surface open area: typically 5% to 15%; minimum thickness: 3 inches for vehicles; minimum compressive strength: 8,000 psi | Concrete pavers conform to ASTM C936 and clay pavers C1272. Reservoir layer required to support the structural load. |
Pervious Concrete |
|
May not require a reservoir layer to support loads, but a layer is required for storage/infiltration. In no case should plain steel rebar or mesh be used in pervious concrete as this invites corrosion. |
Porous Asphalt |
|
Reservoir layer contributes to structural load support. |
There are additional design considerations for permeable pavement, including use of permeable pavement in karst terrain and winter considerations.
A detailed geotechnical investigation may be required for any kind of stormwater design in karst terrain. Permeable pavements, as with other infiltration practices, are not recommended at sites with known karst features as they can cause the formation of sinkholes and can provide a direct link for stormwater to access groundwater without providing any treatment.
Plowed snow piles should be located in adjacent grassy areas so that sediments and pollutants in snowmelt are partially treated before they reach all permeable pavements. Sand is not recommended for winter traction over permeable pavements. If sand is applied, it must be removed with vacuum cleaning in the spring. Traction can be accomplished on PICP using jointing stone materials, some of which will find its way into the joints by springtime. A significant winter advantage of permeable pavements is that they require less deicing materials than their impervious counterparts. Use of deicing material on permeable pavement is therefore not recommended.
Permeable pavements can be used as opportunities for public education with signs explaining how they work. Infiltration demonstrations also help show how the pavements work. Signs provide a reminder to maintenance crews of their presence and list maintenance do’s and don’ts specific to the permeable pavement type.
Design checklists have not been developed for the Minnesota Stormwater Manual. Below are links to checklists developed by other organizations.