<center><font size=3>'''Temporary Sediment Control - Corrective Actions'''</font size><br>
+
<font size=3>'''Temporary Sediment Control - Corrective Actions'''</font size><br>
 
+
Link to this [[Temporary Sediment Control - Corrective Actions|table]]
Link to this [[Temporary Sediment Control - Corrective Actions|table]]</center>
 
  
 
<table class="sortable">
 
<table class="sortable">
Line 9: Line 8:
 
<th>Corrective Action</th>
 
<th>Corrective Action</th>
 
</tr>
 
</tr>
 
 
<tr>
 
<tr>
 
<td>Silt fence</td>
 
<td>Silt fence</td>
<td>Wrong type installed
+
<td>
Installed in wrong location
+
*Wrong type installed
Improper geotextile used
+
*Installed in wrong location
Insufficient geotextile embedment or weighting units
+
*Improper geotextile used
 
+
*Insufficient geotextile embedment or weighting units
Insufficient compaction of soil
+
*Insufficient compaction of soil
Soil turned over, loosened, or both due to inadequate equipment for sliced type
+
*Soil turned over, loosened, or both due to inadequate equipment for sliced type
Inadequate fastenings
+
*Inadequate fastenings
Incorrect post spacing
+
*Incorrect post spacing
Inadequate intra-fence end-joint connections
+
*Inadequate intra-fence end-joint connections
Improperly wrapped under J-barrier
+
*Improperly wrapped under J-barrier
Silt fence left in place when no longer needed
+
*Silt fence left in place when no longer needed
Turbidity barrier missing top interconnect cable
+
*Turbidity barrier missing top interconnect cable
Silt fence type not maintained for function or performance
+
*Silt fence type not maintained for function or performance
 
</td>
 
</td>
<td>Remove and install as shown in plan  
+
<td>
Remove silt fence
+
*Remove and install as shown in plan  
Replace with correct geotextile
+
*Remove silt fence
Reinstall silt fence or apply sandbags or aggregate toe mass
+
*Replace with correct geotextile
Compact soil with tire or plate compactor
+
*Reinstall silt fence or apply sandbags or aggregate toe mass
Compact soil with tire or plate compactor
+
*Compact soil with tire or plate compactor
 
+
*Compact soil with tire or plate compactor
Install more zip-ties
+
*Install more zip-ties
Install more posts
+
*Install more posts
Wrap geotextiles around post to provide seal; else fill gap
+
*Wrap geotextiles around post to provide seal; else fill gap
Reinstall J-barrier
+
*Reinstall J-barrier
Immediately remove silt fence
+
*Immediately remove silt fence
Install interconnect cable
+
*Install interconnect cable
Immediately fix the problem
+
*Immediately fix the problem
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
<tr>
 
<tr>
 
<td>Bale barriers</td>
 
<td>Bale barriers</td>
<td>Not notched in
+
<td>
Not properly staked into the ground
+
*Not notched in
Not properly overlain with RECP
+
*Not properly staked into the ground
 +
*Not properly overlain with RECP
 
</td>
 
</td>
<td>Remove bales and subcut a notch
+
<td>
Add stakes of sufficient length
+
*Remove bales and subcut a notch
Install blanket and anchors
+
*Add stakes of sufficient length
 +
*Install blanket and anchors
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
<tr>
 
<tr>
 
<td>Filter berms</td>
 
<td>Filter berms</td>
<td>Damaged or compacted by equipment
+
<td>
Berm breached or bypassed
+
*Damaged or compacted by equipment
Improper depth to width ratio
+
*Berm breached or bypassed
Rock weeper missing filter aggregate face
+
*Improper depth to width ratio
 +
*Rock weeper missing filter aggregate face
 
</td>
 
</td>
<td>Restore filtration function by soil loosening
+
<td>
Add fill, embed rock buttress, reconfigure drainage
+
*Restore filtration function by soil loosening
Add more fill to conform to berm detail
+
*Add fill, embed rock buttress, reconfigure drainage
Add coarse filter aggregate front side of flow
+
*Add more fill to conform to berm detail
 +
*Add coarse filter aggregate front side of flow
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
<tr>
 
<tr>
 
<td>Floating silt curtain</td>
 
<td>Floating silt curtain</td>
<td>Curtain not end anchored on land or adjacent perimeter control
+
<td>
Curtain not weighted sufficiently in water or for field conditions
+
*Curtain not end anchored on land or adjacent perimeter control
Improper depth(s)
+
*Curtain not weighted sufficiently in water or for field conditions
Improper in-water anchoring/tethering
+
*Improper depth(s)
Curtain left in water beyond temporary in-water work phase
+
*Improper in-water anchoring/tethering
Curtain too far from land edge
+
*Curtain left in water beyond temporary in-water work phase
Navigation buoys not installed with flowing water type
+
*Curtain too far from land edge
 +
*Navigation buoys not installed with flowing water type
 
</td>
 
</td>
<td>Bring end of curtain onto land or close the gap
+
<td>
Install correct curtain, add anchors and cables
+
*Bring end of curtain onto land or close the gap
Install correct curtain depth for in-water ground contact
+
*Install correct curtain, add anchors and cables
Remove and install with proper depths
+
*Install correct curtain depth for in-water ground contact
Immediately remove and install new controls on land
+
*Remove and install with proper depths
Recover and reinstall following detail of 6 ft maximum
+
*Immediately remove and install new controls on land
Install navigation buoys as necessary
+
*Recover and reinstall following detail of 6 ft maximum
 +
*Install navigation buoys as necessary
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
<tr>
 
<tr>
 
<td>Perimeter controls</td>
 
<td>Perimeter controls</td>
<td>Incorrect BMP for location
+
<td>
Not properly J-hooked at termination points
+
*Incorrect BMP for location
 
+
*Not properly J-hooked at termination points
Not placed along contours when feasible
+
*Not placed along contours when feasible
Wrong type installed for intended application
+
*Wrong type installed for intended application
Not maintained for function
+
*Not maintained for function
No redundant practice above water resource
+
*No redundant practice above water resource
 
</td>
 
</td>
<td>Remove and install proper perimeter control
+
<td>
Remove section, install J-hook section and connect upgradient
+
*Remove and install proper perimeter control
Reconfigure control to match slope contour
+
*Remove section, install J-hook section and connect upgradient
Remove and install proper control
+
*Reconfigure control to match slope contour
Immediately apply maintenance to restore function
+
*Remove and install proper control
Add control redundancy
+
*Immediately apply maintenance to restore function
 +
*Add control redundancy
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
<tr>
 
<tr>
 
<td>Sediment control logs</td>
 
<td>Sediment control logs</td>
<td>Not staked properly resulting in undermining or movement of logs
+
<td>
Log ends not overlapped when more than one is needed in a line
+
*Not staked properly resulting in undermining or movement of logs
 +
*Log ends not overlapped when more than one is needed in a line
 
</td>
 
</td>
<td>Install additional stakes
+
<td>
Reconfigure logs for overlap
+
*Install additional stakes
 +
*Reconfigure logs for overlap
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
<tr>
 
<tr>
 
<td>Sandbag barrier</td>
 
<td>Sandbag barrier</td>
<td>Sandbags not butt end jointed to provide seal
+
<td>
Sandbags not sufficiently high
+
*Sandbags not butt end jointed to provide seal
 
+
*Sandbags not sufficiently high
Sandbags not installed on contour
+
*Sandbags not installed on contour
Sandbags not working as a diversion
+
*Sandbags not working as a diversion
Middle of sandbag dike higher than ends
+
*Middle of sandbag dike higher than ends
 
</td>
 
</td>
<td>Re-install sand bags
+
<td>
Add more sand bags in interlocked pyramid style configuration
+
*Re-install sand bags
Re-configure barrier to conform to contour
+
*Add more sand bags in interlocked pyramid style configuration
Re-install with a plastic cover wrap
+
*Re-configure barrier to conform to contour
Reconfigure placement to lower middle or extend upper ends
+
*Re-install with a plastic cover wrap
 +
*Reconfigure placement to lower middle or extend upper ends
 
</td>
 
</td>
 
</tr>
 
</tr>
 
 
 
 
 
 
</table>
 
</table>
 
 
 
 
  
 
[[category:Table]]
 
[[category:Table]]

Revision as of 19:32, 30 October 2016

Temporary Sediment Control - Corrective Actions
Link to this table

Item Corrective Action Required if Corrective Action
Silt fence
  • Wrong type installed
  • Installed in wrong location
  • Improper geotextile used
  • Insufficient geotextile embedment or weighting units
  • Insufficient compaction of soil
  • Soil turned over, loosened, or both due to inadequate equipment for sliced type
  • Inadequate fastenings
  • Incorrect post spacing
  • Inadequate intra-fence end-joint connections
  • Improperly wrapped under J-barrier
  • Silt fence left in place when no longer needed
  • Turbidity barrier missing top interconnect cable
  • Silt fence type not maintained for function or performance
  • Remove and install as shown in plan
  • Remove silt fence
  • Replace with correct geotextile
  • Reinstall silt fence or apply sandbags or aggregate toe mass
  • Compact soil with tire or plate compactor
  • Compact soil with tire or plate compactor
  • Install more zip-ties
  • Install more posts
  • Wrap geotextiles around post to provide seal; else fill gap
  • Reinstall J-barrier
  • Immediately remove silt fence
  • Install interconnect cable
  • Immediately fix the problem
Bale barriers
  • Not notched in
  • Not properly staked into the ground
  • Not properly overlain with RECP
  • Remove bales and subcut a notch
  • Add stakes of sufficient length
  • Install blanket and anchors
Filter berms
  • Damaged or compacted by equipment
  • Berm breached or bypassed
  • Improper depth to width ratio
  • Rock weeper missing filter aggregate face
  • Restore filtration function by soil loosening
  • Add fill, embed rock buttress, reconfigure drainage
  • Add more fill to conform to berm detail
  • Add coarse filter aggregate front side of flow
Floating silt curtain
  • Curtain not end anchored on land or adjacent perimeter control
  • Curtain not weighted sufficiently in water or for field conditions
  • Improper depth(s)
  • Improper in-water anchoring/tethering
  • Curtain left in water beyond temporary in-water work phase
  • Curtain too far from land edge
  • Navigation buoys not installed with flowing water type
  • Bring end of curtain onto land or close the gap
  • Install correct curtain, add anchors and cables
  • Install correct curtain depth for in-water ground contact
  • Remove and install with proper depths
  • Immediately remove and install new controls on land
  • Recover and reinstall following detail of 6 ft maximum
  • Install navigation buoys as necessary
Perimeter controls
  • Incorrect BMP for location
  • Not properly J-hooked at termination points
  • Not placed along contours when feasible
  • Wrong type installed for intended application
  • Not maintained for function
  • No redundant practice above water resource
  • Remove and install proper perimeter control
  • Remove section, install J-hook section and connect upgradient
  • Reconfigure control to match slope contour
  • Remove and install proper control
  • Immediately apply maintenance to restore function
  • Add control redundancy
Sediment control logs
  • Not staked properly resulting in undermining or movement of logs
  • Log ends not overlapped when more than one is needed in a line
  • Install additional stakes
  • Reconfigure logs for overlap
Sandbag barrier
  • Sandbags not butt end jointed to provide seal
  • Sandbags not sufficiently high
  • Sandbags not installed on contour
  • Sandbags not working as a diversion
  • Middle of sandbag dike higher than ends
  • Re-install sand bags
  • Add more sand bags in interlocked pyramid style configuration
  • Re-configure barrier to conform to contour
  • Re-install with a plastic cover wrap
  • Reconfigure placement to lower middle or extend upper ends